Integration

How to Connect an Electricity Meter to the Index AMI? Compatible RS485/RS232 Harnesses

May 27, 2026·8 min read

The Index AMI HW3 connects to each meter via a compatible point-to-point harness: an A+/B−/GND pair between the Index AMI's phoenix connector and the meter's RS485 or RS232 terminal block. This guide documents the wiring and reference images for the compatible harnesses.

Master compatibility table

RefMeterPortProtocolHarness
AMI-01Microstar P2000-D / D2000RJ45_2RS485Validado
AMI-02Microstar P2000-DRJ45_2RS232Validado
AMI-03Microstar P2000-DRJ45_1RS232Validado
AMI-04ISKRA MT174RS485 (DLMS/COSEM)Validado
AMI-05Star DTS27RJ12RS485Validado
AMI-06Landis+Gyr ZMG405RJ12RS232Validado
AMI-08Elster A1800DB9RS232Validado
AMI-09ITRON SL7000RJ45-1RS232Validado

✓ Validated means Noatec tested and certified that wiring with the Index AMI HW3.

Generic RS485 wiring · 3 wires · applies to Microstar, Star and any RS485 meter

Microstar P2000-D / D2000

Family of three-phase industrial meters widely deployed in Colombian utilities. The P2000-D and D2000 share the same RJ45 connector with two physical ports. A single meter can be read via RS485 (recommended for distances greater than 50 m) or RS232 (short range), and the operator can choose either of the two physical RJ45 ports.

AMI-01 — Microstar RS485 (RJ45_2)

Recommended harness for new integrations. RS485 provides immunity to electrical noise typical of industrial panels and reach of up to 1.2 km with category 5e cable.

AMI-01 — Microstar RS485 (RJ45_2)
AMI-01 · Microstar P2000-D / D2000 · RS485 · RJ45_2

AMI-02 — Microstar RS232 (RJ45_2)

RS232 variant on the same physical port as AMI-01. Useful when the meter is already configured for RS232 and you don't want to reprogram it.

AMI-02 — Microstar RS232 (RJ45_2)
AMI-02 · Microstar P2000-D · RS232 · RJ45_2

AMI-03 — Microstar RS232 (RJ45_1)

RS232 variant on the alternative RJ45_1 port. Used when RJ45_2 is already occupied by another peripheral (optical reader, legacy modem).

AMI-03 — Microstar RS232 (RJ45_1)
AMI-03 · Microstar P2000-D · RS232 · RJ45_1

ISKRA MT174

Three-phase meter from ISKRA (Slovenia) with native RS485 interface speaking DLMS/COSEM over IEC 62056. ONAC-approved and massively deployed in Colombian utilities. The family includes MT171/ME171 models (older, same interface) which are also compatible with this same harness.

Visualization · RS485 wiring ISKRA meter → Index AMI HW3 gateway

AMI-04 — ISKRA MT174 RS485

AMI-04 — ISKRA MT174 RS485
AMI-04 · ISKRA MT174 · RS485

External power required: the ISKRA MT174 cannot be powered from the meter bus. It requires an external 5–15 V source connected to the gateway. Do not connect the VCC pin of the communication connector — the animation explicitly shows this restriction.

Default DLMS/COSEM parameters

ParameterValue
Serial speed9600 bps (typical) — up to 38400 bps
Data bits / parity / stop8 / N / 1
DLMS address (Client SAP)16 (Public Client)
Authentication mechanismLow Level Security (LLS)
OBIS active energy total1.0.1.8.0.255

The OBIS code (Object Identification System) uniquely identifies each meter magnitude with 6 dot-separated numbers — for example 1.0.1.8.0.255 is total imported active energy. For the complete DLMS/COSEM protocol and object model detail, see the linked article at the end.

Star DTS27

Three-phase meter from Star (China) with a 6-contact RJ12 port. Speaks a Modbus RTU dialect over RS485 at 9600 bps. It is one of the most affordable meters in the AMI market and is used in rural cooperative projects and unregulated markets.

AMI-05 — Star DTS27 RS485

AMI-05 — Star DTS27 RS485
AMI-05 · Star DTS27 · RS485 · RJ12

The harness includes a 300 mm RJ12 patch cord connecting the gateway's phoenix connector to the meter's RJ12. Note that it is Modbus RTU, not DLMS — energy registers are in holding registers 0x4000 (total active energy) and following.

Landis+Gyr ZMG405

Industrial three-phase meter from Landis+Gyr (Switzerland). Supports DLMS over RS232 via the optical port and over RS485 with an expansion module. This validation covers only the native RS232 port (RJ12).

AMI-06 — Landis+Gyr ZMG405 RS232 (RJ12)

AMI-06 — Landis+Gyr ZMG405 RS232
AMI-06 · Landis+Gyr ZMG405 · RS232 · RJ12
Visualization · RS232 wiring Landis+Gyr ZMG405 meter → Index AMI HW3 gateway

RS232 is point-to-point: one meter per gateway. If your installation requires multiple Landis+Gyr meters on a bus, use the E350 / E650 family with an RS485 module and request a custom harness.

Elster A1800

Three-phase Elster meter with RS232 interface over a DB9 connector. Speaks DLMS/COSEM over IEC 62056 and is common in European and Latin American utility distribution networks. The AMI-08 harness is a 30 cm cable with a female DB9 connector at the meter end and a phoenix connector at the gateway end. 3 wires: TX (green), RX (red), GND (black).

Visualization · RS232 wiring Elster A1800 meter → Index AMI HW3 gateway

AMI-08 — Elster A1800 RS232 (DB9)

3 wires: TX → RX, RX → TX, GND → GND. 30 cm AWG 22 cable. Female DB9 connector on the meter (pin 3 = TX, pin 2 = RX, pin 5 = GND). DLMS/COSEM protocol — same configuration parameters as the ISKRA MT174 and ITRON SL7000.

AMI-08 — Elster A1800 RS232 (DB9)
AMI-08 · Elster A1800 · RS232 · DB9

ITRON SL7000

Three-phase meter from ITRON with native RS232 interface over an RJ45 connector. Speaks DLMS/COSEM over IEC 62056 and is widely deployed in utilities and retailers. The AMI-09 harness uses an RJ45 patch cord cut to 30 cm — one RJ45 connector is kept at the meter end while the other end is stripped 2.5 cm to connect to the gateway phoenix connector.

Visualization · RS232 wiring ITRON SL7000 meter → Index AMI HW3 gateway

AMI-09 — ITRON SL7000 RS232 (RJ45-1)

3 wires: TX → RX, RX → TX, GND → GND. The RJ45 patch cord is cut to 30 cm with the RJ45 connector towards the meter. DLMS/COSEM protocol at 9600 bps — same parameters as the ISKRA MT174.

AMI-09 — ITRON SL7000 RS232 (RJ45-1)
AMI-09 · ITRON SL7000 · RS232 · RJ45-1

Meter not listed

If your meter is not in this table but exposes RS485 or RS232 with DLMS/COSEM or Modbus RTU, Noatec manufactures custom harnesses. Send the meter's technical datasheet (with the serial port pinout) to soporte@noatec.co.

Next steps

With the harness connected, the next step is to configure the protocol and reading parameters from the app. See the Index AMI configuration guide for detailed steps using the Android app or the desktop tool.